Load Cells for Overload Protection of Cranes: Form Before Accuracy

Robin
November 18, 2026 33 min read
Load Cells for Overload Protection of Cranes: Form Before Accuracy
Load Cells for Overload Protection · Selection Notes

Load Cells for Overload Protection: Pick the Form, Not the Accuracy

Every inquiry for load cells for overload protection arrives asking for accuracy. The specification that actually decides whether the device is legal is the mounting point and the trip point, and both are fixed before I quote anything. Here is how I work through it in the first fifteen minutes of a call.

Robin Kao
VektorForce  ·  November 18, 2026  ·  9 min read
Load Cells
Cranes
Safety Devices

Four thresholds, and only one of them is about the sensor

Load cells for overload protection are never the whole device. A crane limiter is a two-part product: a strain-gauge load cell that measures the hook load, and a controller that compares that reading against a threshold and cuts the hoist circuit. GB 12602-2009 sets the thresholds, and when I read the clause list next to a customer’s requirement sheet, the requirement sheet is usually the looser of the two.

The four thresholds that matter to a sensor supplier are these. At 90 % of rated capacity the device gives an audible and visual pre-warning. At 105 % it alarms continuously and, after a delay of one to two seconds, the relay drops out and cuts hoisting power. Between 110 % and 130 % the relay acts immediately, with no delay at all. And the sensing element itself must survive a 1.5× rated capacity overload without losing its calibration.

Notice what is absent from that list. There is no accuracy figure for the load cell anywhere in it. The device-level tolerance is a display accuracy better than 5 % of full scale and an action error better than 3 % of full scale, which is why the transducer only has to reach 0.1 % to 0.5 %. On a 10 t crane, 3 % is 300 kg of permitted action error; a 0.5 % cell contributes 50 kg of it, one sixth of the budget. The other five sixths belong to the controller, the relay, and the mechanical compliance of whatever the cell is bolted into.

The delay is the reason a cheap cell is not good enough

Between 105 % and 110 % the limiter deliberately waits one to two seconds before cutting power, so a momentarily snatching load does not stop a lift that is perfectly safe. During that wait the overload is real and the cell is carrying it. A cell chosen on accuracy alone and rated just above the static hook load will be living inside its own overload band twice a shift — which is why the 1.5× figure above is a requirement, not a margin.

This is also where selection diverges from the article I wrote earlier on how overload protection is specified on hoisting machinery, which works through the standards map and the error budget in full. That piece answers what the numbers are. This one answers which sensor form a given machine forces you into, and what each choice costs.

One more thing belongs in this section, because it decides how much the sensor matters at all. The thresholds above are set for a machine, not for a sensing point. Whatever the cell reads has to be converted back to hook load before the controller compares it to 90 %, 105 % or 110 %, and that conversion is a single constant — the share of the hook load that reaches the cell. Get the constant right and a 0.5 % cell is more than sufficient. Get it wrong and the most accurate transducer on the market produces a limiter that cuts out at the wrong moment, which is exactly what happened in the chain-hoist case below.

So my ordering of the specification work is deliberately unfashionable. First the machine: what it is, where the structure allows a sensor to sit, and how the rope is reeved. Second the threshold: which setpoint the standard permits for this machine type, and what action error the controller claims. Third, and only third, the sensing element: form, capacity, and the mechanical interface that has to survive the trip event. Customers usually arrive with the third step already decided and the first two blank, and the blank ones are the ones that fail inspection.

Five forms, and the machine that picks each one

Five sensor forms appear in this application. They are not interchangeable, and the ordering is not a matter of preference: the machine’s existing structure decides for you. If the machine has a removable pin in the load path, a shaft pin is available. If it does not, that entire family is closed off, and no amount of engineering on my side reopens it.

Shaft pin (shaft-pin load cell). A load cell machined as a pin. It replaces an existing pivot in the load path and measures the shear across it. Available on tower cranes, hoists and gate hoists (hoists with a pin-coupled sheave block), rack-and-pinion construction hoists, port machinery, and chain hoists. This is the only form that also reads horizontal force when the pin sits on a non-vertical load path, which is why it dominates on tower cranes.

Side-pressure (rope tension) load cell. Clamps onto a rope at its dead end and reads the tension by pressing the rope sideways against a sensing beam. It is the standard fit for electric hoists and rope falls, and its great advantage is that it touches nothing structural: the rope is already there, and the dead end already has to be anchored. It reads one rope leg, never the hook load, and that distinction causes more sizing errors than any other in this application.

Bearing-housing load cell. Replaces the bearing seat under the drum shaft, on bridge and gantry cranes and other machines built with a bearing pedestal. Flat, low-profile, double-shear, tolerant of side load and shock, and available over a wide range. It is the form I reach for when the crane has no accessible pin and the customer will not modify the rope.

Fish-back load cell. Mounts under the fixed-sheave axle, and on equaliser axles where an axle is shared. Used on bridge and gantry cranes and gate hoists. Structurally it is the gentlest option, because the fixed sheave axle is already a load-bearing member sized for the whole rope load.

Plate-ring load cell. A plate with a ring boss, hung in tension in place of the hook or between hook and block. Historically common on electric hoists, now largely displaced by the side-pressure form. I still supply it, but I have not quoted one for a new overload limiter in years, and I say so rather than push it.

Two of these five — the plate-ring and the side-pressure — measure a rope or a link in series with the load. Three of them — shaft pin, bearing housing, fish-back — replace a structural element and measure the force passing through it. That split matters more than any specification on the datasheet, because it determines what fraction of the hook load the sensor actually sees.

Read the same five forms by machine type and the mapping is nearly one-to-one. Tower cranes, gate hoists, rack-and-pinion construction hoists, port machinery and chain hoists take a shaft pin, because every one of them has a removable pin somewhere in the load path — in the hook, the sheave block, the wedge socket or the slew connection. Electric hoists and straight rope lifts take the side-pressure cell at the rope’s dead end. Bridge and gantry cranes take a bearing-housing or fish-back cell, because their pins are captive in welded housings and the rope is best left alone; the fish-back goes under the fixed-sheave axle or an equaliser axle, the bearing housing under the drum shaft. An older electric hoist whose rope cannot be touched is the one case left where a plate-ring cell is still the right answer.

That mapping is the first question I ask in every lifting inquiry — not the capacity, not the accuracy, just the machine. A customer who names the machine has done half the selection before I pick up a datasheet, and a customer who names the sensor first usually has to go back and name the machine.

The mounting point is a multiplier, not a detail

Take one crane, one 10 t hook load, and four candidate mounting points for a load cell. The force at each point is different, and it is different by a factor that dwarfs everything the datasheet talks about.

A pin above the hook sees the whole load: 10.00 t. Two pins on an equaliser axle share it, so each sees 5.00 t. A cell on the dead end of a two-fall reeving sees one rope leg at 5.05 t. The same cell on a four-fall reeving sees 2.58 t — and if someone quotes a unit for the two-fall machine and installs it on the four-fall one, the reading is not wrong by a few percent, it is wrong by roughly half.

The fixed sheave is worse, because it does not read a rope tension at all. It reads the vector sum of both rope legs leaving the sheave, which is 2T × sin(θ/2) for a wrap angle θ. With a 5 t leg tension, a 180° wrap gives 10.0 t, a 120° wrap gives 8.66 t, and a 90° wrap gives 7.07 t. Nothing changed except the geometry of the reeving, and the reading moved by 29 %.

This is the reason I ask for a reeving diagram before I ask for an accuracy figure. On a fixed-sheave installation I need three things and I need them in writing: the wrap angle, the number of falls, and the sheave diameter. Without the wrap angle I cannot tell the customer what his own cell is measuring, and neither can anyone else.

Sheave diameter earns its place on that list for a reason that has nothing to do with trigonometry. A rope bent over a small sheave develops higher local stress in the outer wires, and a side-pressure cell clamped close to a tight bend sees the rope in a stiffer, less settled condition than one clamped on a long straight run. It is a second-order effect next to the wrap angle, but on a machine that cycles tens of thousands of times a year it is the difference between a stable zero and one that walks.

There is a companion problem on the pin side, and it catches out even experienced machine builders. A shaft pin replaces a pivot, and a pivot is usually retained by something — a circlip, a shoulder, a keeper plate welded to the housing. When the pin is replaced, the retaining feature has to be replaced too, and on a load pin it also has to hold the pin’s angular orientation, because the strain gauges inside are bonded to a specific axis. A pin that rotates freely in its bore is not measuring the load any more; it is measuring whatever component of the load happens to align with the gauges at that moment, and the reading drifts as the pin turns. An H7/g6 fit plus a keeper plate is the minimum, and I put the required orientation on the drawing rather than in an email.

Both of these — the reeving constant and the pin orientation — are mechanical facts about the machine that no amount of electronics can correct later. They are also free to fix at the drawing stage and expensive to fix in the field.

The question that ends most sizing arguments

“On the drawing, what does this pin hold up when the hook has nothing on it?” If the answer is not near zero, the pin is not in the hook load path, and the whole calculation starts again. I have had a customer send me a beautifully dimensioned pin drawing on a machine where that pin carried the counterweight frame.

The setpoint that cannot legally be set

Here is an arithmetic trap that appears in maybe one in five requirement sheets I receive, and it is worth walking through slowly because it is invisible until an inspector finds it.

GB 12602 sets the allowed trip-point band by machine type. For tower cranes the setpoint falls between 105 % and 110 % of rated capacity. For mobile cranes it is 100 % to 110 %. Separately, the action error — how far the actual trip lands from the setpoint — must stay within ±3 % for a combined limiter and ±5 % for an automatic-stop limiter.

Now combine them. A tower crane with a combined limiter set at 105 % will actually trip somewhere between 102 % and 108 %, and that is legal. Set it at 108 % and the trip band becomes 105 % to 111 % — it can now act above the 110 % ceiling. Set it at 110 %, which a surprising number of customers ask for because “we want the full capacity before it stops”, and the band is 107 % to 113 %. The device can leave the factory already outside its own legal envelope, before anyone has touched the machine.

The highest defensible setpoint on a tower crane with a ±3 % limiter is therefore 107 %, and the comfortable one is 105 %, which is where the standard’s own delay clause sits. When a customer insists on 110 %, what he is asking for is not extra capacity. On a 10 t crane he is asking for the right to lift about 300 kg more than he is allowed to, and to have the paperwork say it is fine.

I say this on the first call, and occasionally it costs me the order to a supplier who did not. I would rather lose that order than ship a limiter that a third-party inspector will fail on the setpoint calculation alone.

The same arithmetic applies one level down, to the temperature band, and it is where I see the second most common specification gap. A load cell specified at 0.05 % F.S per 10 °C of temperature effect on output is a normal, honest figure. On a 10 t range, 0.05 % is 5 kg per 10 °C. Over a 40 °C spread from a cold morning to a sunlit afternoon on a quay, that is 20 kg of drift on a device whose entire permitted action error is 300 kg. It is not fatal, and it is not nothing: it is roughly one fifteenth of the budget spent on the weather, before a single kilogram of real error has been added. A cell compensated over a narrow band and installed outdoors will spend half the year outside its compensation, and the certificate will not say so.

Which is why I ask where the machine lives before I ask what it lifts. Port and quay machines, construction hoists and anything on a jetty are a different specification from a crane inside a heated workshop, and the difference shows up in the temperature coefficient and the ingress rating, not in the accuracy class.

Sizing the range from the trip event, not the hook load

The capacity of an overload-protection load cell is not chosen from the rated hook load. It is chosen from the worst thing that will happen to the cell while the limiter is deciding whether to act.

Start from the static force at that mounting point, from the previous section. Multiply by the hoisting dynamic factor, which accounts for the snatch when a slack rope comes taut — 1.20 is the figure I use for a general-purpose crane, and it is low for a machine that regularly lifts off the ground. That product is the load the load cell will see on a normal lift, before any overload exists.

Then add the standard’s own requirement: the load cell must take 1.5× rated capacity without harm. Put the two together and the rule becomes simple. The load cell’s rated capacity should be at least the static force at the mounting point, times the dynamic factor, with its safe overload covering the trip event itself. On an equaliser pin carrying 5.00 t static on a 10 t crane, 5.00 × 1.20 = 6.00 t on every lift, and a 6 t cell would be sitting at 100 % of its rating before the limiter has done anything at all. The 10 t cell is the one that survives the job, and it costs less than the argument about why the 6 t cell cracked.

Two corollaries I apply to every quote. First, a load cell whose rated capacity is very close to the static load will be operating inside its own creep and temperature bands permanently, and the readings will drift with the weather. Second, if the answer to the sizing calculation is that no standard cell fits the space available, that is a custom pin or a custom housing, not a smaller load cell with a longer warranty discussion.

From millivolts to a cut power line: what the controller does

The limiter is a chain, and the load cell is only its first third. The cell’s bridge outputs a few millivolts per volt of excitation; the weighing controller amplifies and filters that signal, compares it against the thresholds in the first section, and drives a relay that sits inside the hoist control circuit. When the relay drops, the hoist loses power and the alarm sounds. Neither half is a limiter on its own: a cell without a controller is a measuring instrument, and a controller without a correctly placed cell is a very confident guess.

Where the controller lives decides what the cell has to output. On most cranes the controller sits in the operator’s cab or above the control button station, which on a port crane or a tall gantry means a cable run of tens of metres. A bare bridge signal over that distance picks up noise from the motors and the slip rings, so for long runs I specify a cell with a built-in converter — 4–20 mA or RS-485 — or a junction box with a summing board when the machine carries more than one cell. On a short run inside a hoist body, the raw bridge signal is simpler and one less thing to fail. This choice is part of the cell specification, not an afterthought, and it is the piece most often forgotten when someone orders a sensor alone.

The relay logic mirrors the four thresholds, and one detail in it is worth more than all the rest. The limiter must cut the unsafe direction — hoisting up, or increasing the radius — while still allowing motion in the safe direction, so the operator can lower the load and set it down. A controller that cuts everything strands the load in the air, which is its own emergency. When I am asked to match a cell to an existing controller, the first thing I confirm is that this asymmetric behaviour exists in its relay wiring, because the cell cannot supply it and the standard requires it.

Two controller features I tell every customer to ask for, because they cost nothing extra and change what the device is worth after an incident. Peak-hold, so the display shows the true maximum of a snatch rather than whatever the eye caught. And an overload history — some controllers log several thousand events — which settles the argument about what happened long before anyone reconstructs it from memory.

What I hand over at the end of this chain is a one-page interface sheet: the cell’s rated sensitivity, zero balance, input and output resistance, recommended excitation, cable length and calibration constant expressed in the units the controller will display. The controller belongs to your limiter supplier; the interface between us is that sheet, and it is why I will not quote a load cell before the controller is known.

A 5 t chain hoist that tripped at 4.2 t

A distributor in Southeast Asia came to me with an electric chain hoist problem that had already been through two suppliers. A 5 t hoist was cutting out at what the operator swore was a 4.2 t load. The limiter was replaced once, then the cell, then the controller. The complaint persisted.

I asked for the reeving. The hoist was a four-fall machine, and the load cell was a side-pressure unit clamped to the dead end of the rope. The installer had sized it for the hook load, which is the intuitive thing to do: 5 t hoist, 5 t cell. But on a four-fall machine each rope leg carries a quarter of the hook load, so at a genuine 4.2 t hook load the dead-end leg was at about 1.05 t — and the controller had been calibrated against a hook-load scale, not against the leg.

The load cell was not faulty. The number it produced was correct, in the units it was measuring, and the calibration constant applied to it was wrong by a factor of four. That is a configuration error, and it is invisible on any test bench, because the bench has no reeving.

The fix took an afternoon and no new hardware: recalibrate the controller against a known hook load with the actual reeving in place, then verify at three points — the 90 % pre-warning, the 105 % delayed trip, and one point above 110 % to confirm the relay drops immediately. The distributor now sends me a reeving photograph with every hoist inquiry, which is the best outcome I could have asked for.

What I took from it: on any multi-fall machine, the sensor and the controller must be calibrated together, on the machine, with the rope in its working configuration. A load cell with a certificate is not a calibrated limiter.

I also changed how I quote these hoists. The quotation now carries the reeving constant in writing — “this cell reads one quarter of the hook load on your four-fall arrangement” — so that whoever commissions the limiter has the number in front of them rather than deriving it from a drawing at six in the evening. It costs me one line on a document and has prevented at least three repeat visits.

A tower crane where two pins would have halved the signal

A tower crane builder in the Gulf sent a drawing of the equaliser axle under the hook block and asked for two shaft pins, one at each end, each rated to the full hook load. It is a generous specification, and it would have doubled his cost for no benefit, so I asked a question instead of quoting.

The two ends of that axle share the load. Two pins rated at the full hook load each means each pin is running at 50 % of its rating on a normal lift, so at the 105 % delayed trip the pins are at about 52 % — the overload protection is being provided by a device operating in the middle of its range, where nothing is being stressed and nothing needs to be. He was buying capacity he would never use and would never be able to demonstrate.

The larger issue was different: he had no anti-rotation feature on the drawing. An equaliser pin that can rotate in its bore loses the axis it is measuring, and the reading walks away from the truth without anything failing visibly. We added a keeper plate and specified an H7/g6 fit, and I sent a dimensioned drawing back with the pin orientation marked, because “install with the cable exit pointing down and outboard” is the kind of instruction that gets lost in a purchase order.

He ordered the two pins sized to the equaliser share, not the hook load, and the saved budget went into the controller. Both of us ended up with a better device.

There is a version of that conversation I have more often, where the customer has already built the equaliser to take two full-load pins and does not want to hear that the specification is generous. In that case I quote what he asked for and add one sentence: the pins will run at half their rating, so the limiter will be reading a small signal in the bottom half of the range, and the calibration will be correspondingly more sensitive to zero drift. Sometimes he changes his mind, sometimes he does not. Either way the sentence is in the file, and when the zero wanders two years later nobody has to reconstruct why.

Retrofitting a limiter onto a 1990s gantry crane

The hardest version of this job is not a new machine. It is a gantry crane built before anyone thought about sensor access, where the customer has been told by an inspector that he needs a limiter and has four weeks to fit one.

On that crane there was no accessible pivot pin — every pin in the load path was captive in a welded housing — and the customer would not permit the rope to be cut for a side-pressure installation. That removed the shaft pin and the rope cell in one sentence, and left the bearing housing and the fish-back form. We went with a bearing-housing load cell under the drum shaft bearing seat, which required machining the existing pedestal flat and drilling four holes.

Three things decided whether it worked, and none of them were the sensor. The pedestal had to be flat within a small fraction of a millimetre, because a bearing-housing cell bolted onto a distorted seat measures the distortion as load. The original bearing seat had to be shimmed back to its former height so the drum did not change alignment. And the cable route had to be planned before the cell was fitted, because on that crane the only path from the bearing pedestal to the cab ran past a walkway that people used.

The load cell was the easy part of the project and the cheapest line on the invoice. I have stopped being surprised by that.

Two lessons from that job went into my standard answer afterwards. The first is that on a retrofit the survey has to be a survey, with a straight-edge on the pedestal and a tape measure on the cable route, not a photograph and a phone call. The second is that a retrofit is always a joint design: I can specify the cell and the interface, but the machining, the shimming and the cable route belong to whoever is standing on the crane, and if they are not in the conversation from the beginning the cell arrives into a space that was never prepared for it.

It also taught me to price the survey separately and charge for it. Not because the money matters, but because a customer who has paid for a survey reads it.

What I supply and what I do not

This distinction is the one I make on every inquiry, and it is the reason I can be useful on a safety device without ever claiming to certify one.

  • I supply the load cell in whatever form your structure allows — shaft pin, side-pressure, bearing housing, fish-back, or plate ring — sized from your drawing, with the mechanical interface specified, plus the junction box and cabling. I also supply the matched calibration data, so your controller integrator starts from a known reference rather than a nominal sensitivity.
  • I do not supply the overload limiter as a certified device. The controller, the relay logic, the trip-point setting, the type approval and the machine’s conformity all belong to you or to your limiter supplier. I do not issue a certificate for a limiter, because I do not build one.
  • I do not supply safety-rated or redundant-channel components, and I will not describe a standard industrial cell as one. If your application needs a performance-level architecture with diagnostics and redundancy, that is a different product from a different supplier, and I will say so before you spend money with me.

Two more things I decline, because they come up often enough to be worth writing down. I do not certify the machine: whatever the cell measures, the lifting capacity, the structure and the CE or type-approval status of the crane are the OEM’s. And I do not supply a load cell for an application where it would be the only overload protection on a machine carrying people — that is an architecture decision, not a component decision, and it needs to be made above my pay grade.

There is a third refusal that surprises people more. I will not quote a load cell for a limiter whose controller has not been chosen yet. It sounds like obstruction and it is not: the load cell’s output, its excitation, its bridge resistance and its cable length all have to suit the input of a specific controller, and a cell bought first becomes a constraint on everything bought after it. Twice I have been handed a limiter that was already on site with a cell that could not be matched to it, and both times the cheapest fix was a new load cell rather than a new controller.

The one place I do push back the other way: if a customer has a limiter controller he is happy with and only needs the load cell replaced, that is the easiest job I get all year. Send the controller model, the excitation voltage, the sensitivity it expects and the connector, and the rest follows.

The five forms I quote, and where each one belongs

WST701 shaft pin load cell for crane overload protection

WST701 — shaft pin

50 N to 1000 kN, stainless or alloy steel, ±0.5 % F.S., IP66. Made to your pin diameter and length, so it drops into an existing pivot bore. Tower cranes, gate hoists, port machinery, chain hoists. Needs an anti-rotation keeper.

View WST701 →

WST702 wire rope tension load cell for hoist overload limiting

WST702 — rope tension

10 to 200 kN in five steps, ±0.3 % F.S., IP66, stainless or alloy steel. Clamps the rope at its dead end, so no structural modification. Electric hoists and rope falls. Reads one leg, not the hook load — the fall count is the calibration constant.

View WST702 →

WST403 plate ring tension load cell for hoist overload limiter

WST403 — plate ring

2 to 100 t, 20 to 2000 kN, ±0.03 to 0.1 % F.S., 150 % safe and 200 % ultimate overload, IP66. Hangs in series with the hook, so it reads the whole load with no reeving correction. Still specified on new electric hoists, though less often than it used to be.

View WST403 →

WST1402 bridge type double ended shear beam load cell for bearing housing weighing

WST1402 — bridge / bearing housing

15 to 100 kN, 0.3 to 0.5 % F.S., alloy steel, IP67, double-ended shear beam with a symmetrical structure. Fixed at both ends, loaded in the middle. Bridge and gantry cranes where the bearing seat can be machined flat. Tolerates side load and shock better than a pin.

View WST1402 →

Custom fish back load cell under fixed sheave axle for crane overload protection

Fish-back set — under the fixed sheave

A matched pair for the fixed-sheave axle or the equaliser axle, sized to the sheave load rather than the hook load. Built to the axle diameter and the wrap angle you give me. The gentlest option on an old machine, because the axle already carries the whole rope load.

Ask for a custom set →

For the wider question of how these devices are specified, tested and certified on hoisting machinery, see my earlier article on specifying overload protection. For machines that weigh rather than protect, the same shaft-pin and tension forms appear in lifting platforms.

One note on how to read those five cards. The capacities are not a ladder and there is no “best” model among them. The WST701 shaft-pin load cell and the WST1402 bridge load cell replace structure, so they are sized by the force at their own mounting point. The WST702 and WST403 tension load cells sit in series with the load, so they are sized by the load itself. A customer who asks for “the cheapest one that will do 10 t” has asked a question that has no answer until the mounting point is known.

Frequently asked questions

What accuracy does an overload protection load cell need?

0.1 % to 0.5 % of full scale is enough, because the device-level tolerance in GB 12602 is a display accuracy better than 5 % of full scale and an action error better than 3 %. A 0.5 % load cell on a 10 t crane contributes 50 kg against a 300 kg action-error budget. Spending more on accuracy buys nothing the operator can see; the better purchase is a stronger cell.

Which sensor form should I choose for a bridge crane?

Bearing-housing or fish-back, in that order of preference. A bridge or gantry crane usually has no accessible pivot pin in the load path, which rules out a shaft pin, and cutting the rope for a side-pressure unit is rarely acceptable. The bearing-housing cell replaces the bearing seat under the drum shaft; the fish-back cell goes under the fixed-sheave axle.

Why does my hoist limiter trip below the rated load?

Almost always a reeving constant, not a faulty load cell. On a four-fall machine the cell at the dead end reads about a quarter of the hook load, and if the controller is calibrated for hook load the trip lands at roughly a quarter of the intended point. Recalibrate against a known hook load with the rope in its working configuration.

Can the limiter be set at 110 % of rated capacity?

Not safely on a tower crane. The setpoint band is 105 % to 110 % and the action error is up to ±3 %, so a 110 % setpoint can trip anywhere between 107 % and 113 % — above the legal ceiling. The highest defensible setpoint is 107 %, and 105 % is where the standard’s own delay clause sits.

What overload capacity does the sensor itself need?

The load cell must survive 1.5 times rated capacity without losing calibration, and it should be sized from the static force at the mounting point times the hoisting dynamic factor — 1.20 for a general-purpose crane. A load cell sized at the static load will spend its life inside its own overload band, because the 105 % delayed trip holds the overload for one to two seconds.

Do I need a custom shaft pin or a standard one?

Custom, almost always. A shaft pin replaces an existing pivot, so its diameter, length, shoulder position and cable exit are fixed by the machine, not by a catalogue. Standard sizes exist for the 1 t to 5 t range; above that I work from your drawing, and the drawing has to state the force direction.

Does the cell need to be IP68?

Port and quay machines, construction hoists and wash-down areas: yes, and a filled or potted body rather than a sealed one. Indoor workshop cranes are usually fine at IP66 or IP67. What fails in service is rarely the rating on the label, it is the cable entry, so specify the gland and the strain relief with the same care as the cell.

Can you supply the complete limiter, certified?

No. I supply the load cell, the junction box and the cabling, plus matched calibration data. The controller, the relay logic, the trip-point setting and the type approval belong to your limiter supplier, and the machine’s conformity belongs to the OEM. I also do not supply safety-rated or redundant-channel components.

Send me the pin drawing, not the accuracy figure

Pin diameter and bore length, the reeving diagram, the rated capacity and the machine type, plus your annual volume. I will tell you which of the five forms your structure actually allows and quote it within 12 hours — trial orders welcome.

Email info@vektorforce.com

Setpoint bands, error limits and the 1.5× overload requirement are taken from GB 12602-2009 and from the limiter technical requirements used in this industry; confirm them against the edition your market applies. Selection figures are worked examples, not a substitute for a check against your own machine drawing.